The Difference Between Normally Closed and Normally Open Solenoid Valves

A solenoid valve is an electromechanical device used to control the flow of liquids or gases in a system. The configuration of these valves can be classified into two primary types: normally open (NO) and normally closed (NC).

Understanding the differences between Normally Open and Normally Closed solenoid valves is crucial for selecting the right valve for your application, ensuring efficiency, safety, and reliability. Read on to explore the functional distinctions, advantages, and common uses that will guide you towards making an informed decision for your system’s needs.

What is a Solenoid Valve?

A solenoid valve is an electromechanically operated valve that uses an electric coil, known as a solenoid, to change the state of the valve from open to closed or vice versa. The solenoid acts upon a plunger or pivoted armature which, in turn, operates the valve mechanism. As electrical current passes through the coil, it generates a magnetic field that triggers motion within the plunger. This action either opens or closes the valve depending on its design and purpose.

This type of valve is widely employed in fluid power pneumatic and hydraulic systems, enabling them to be controlled remotely or automatically. Solenoid valves are ideal for quick and reliable switching operations aiming at controlling various types of gases and liquids. Their designs can be simple or sophisticated, allowing for use in industrial applications, home appliances, automobiles, and more.

what is Normally Open Solenoid Valve

A normally open solenoid valve, in its default state, allows fluid or gas to flow through it. It is designed such that when de-energized, the valve is open and the passage for media is clear, enabling continuous flow. These valves are actuated by electromagnetic forces generated when an electric current passes through a coil within the valve assembly. The magnetic field produced thereby exerts force on the plunger or armature linked to the valve’s internal components.

Upon energization, the force pulls the plunger against a seat or opening, thus interrupting flow as the valve closes. When power is cut off, springs or other mechanical means within the solenoid return it to its normal open position. This default open configuration can be particularly advantageous in applications where maintaining a default flow condition is critical for safety or process requirements.

For instance, in cooling systems or applications involving gas delivery where interruption could lead to overheating or pressure build-up respectively, a normally open configuration ensures that any failure of electrical power will not impede flow.

FeatureDescription
Default StateOpen (allows flow)
Energized StateClosed (interrupts flow)
MechanismElectromagnetic force moves plunger upon energization
Power Failure ResponseRemains open (safety feature for uninterrupted flow)
Typical ApplicationsSafety systems, cooling systems, gas delivery
Functional AdvantageEnsures continuity of flow even with power disruption

What is Normally Closed Solenoid Valve

A normally closed (NC) solenoid valve is a type of electrically-operated valve that remains closed when de-energized. In its default position, the flow of media through the valve is blocked, and it requires an electrical current to actuate or open. The working principle involves an electromagnetic solenoid coil which, when energized, creates a magnetic field that lifts a plunger or armature inside the valve. This movement retracts the seal from the valve orifice and allows fluid or gas to pass through.

The design of normally closed solenoid valves ensures they provide a secure shut-off in their resting state, making them suitable for safety-critical applications where preventing flow without power is necessary. Additionally, due to their fail-safe operation in power loss conditions, NC valves are frequently used in systems requiring conservative energy use and those that must maintain certain conditions should a power failure occur.

FeatureDescription
Default PositionClosed
OperationRequires electrical current to open
PrincipleElectromagnetic coil actuates plunger/seal
SuitabilityBlocking flow in resting state; Preventing flow without power
Medium CompatibilityAir, Water, Oil
BenefitSecure shut-off capability; Conserves energy during downtime

How to Choose Between Normally Open and Normally Open (Failure State, Energy Conservation)

When deciding between a normally open (NO) solenoid valve and another normally open configuration, particularly regarding the failure state and energy conservation, one must analyze the application’s demands. For operations where it is safer or preferable for a valve to remain open on power failure, an NO solenoid valve might be ideal. This ensures that in case of an unexpected loss of power, processes that require continuous flow—such as cooling systems or gas delivery services—aren’t interrupted.

Energy conservation is another vital consideration. A solenoid valve requires power to change its state. If an application mostly needs a valve to stay in an open position, choosing an NO solenoid will save energy since it won’t require electricity to remain in its default position. Conversely, if the application typically requires a closed valve, then selecting a normally closed option would conserve energy for the same reasons.

Consideration should also be given to the duty cycle of the system; if the duty cycle is high, using an NO solenoid may prevent unnecessary heat generation and potential burnout due to prolonged activation.

In summary:

  • For safety reasons, choose an NO solenoid valve if it’s critical that the valve remains open during a power outage.
  • For energy efficiency, select an NO solenoid valve if the operational standard state is ‘open.’
ConsiderationNormally Open Advantage
Failure StateValve remains open during power failure; essential for systems requiring continuous flow with minimal interruption risks.
Energy ConservationSaves energy when default ‘open’ position aligns with operational norms because no power is needed to hold the valve open.
Operational SafetyEnsures safety precautions by defaulting to a fail-safe state when necessary for specific processes or work environments.
Duty Cycle & Heat GenerationAn NO solenoid minimizes heat production through reduced energization time which could lead to less wear and increased lifespan.

3-Port Valves

3-port solenoid valves are versatile components used in various fluid control applications. These valves have three connections and two orifices and are capable of directing flow between different ports based on their design and the state of actuation. A typical configuration includes one inlet, one outlet, and one exhaust port.

In their default state, these valves can be either normally open (NO) or normally closed (NC), with the exhaust port usually being at atmospheric pressure when de-energized. The role of the third port is what differentiates them from their 2-port counterparts; it facilitates an additional pathway for the medium to flow to or from an alternate destination.

When energized, a 3-port valve might be configured to either block all ports (in a closed-center position), connect two specific ports while blocking the third (open-center position), or allow pass-through between all ports (tandem-center). This variety allows for more complex control schemes in pneumatic or hydraulic systems such as switching between two circuits, maintaining pressure in one part of a system while venting another, or even acting as a diverter valve.

Selection factors for a 3-port solenoid valve include not only the normal state but also the desired action upon energization, media compatibility, required flow rates, working pressures, voltage specifications and environmental conditions.

FeatureDescription
Number of PortsThree (inlet, outlet, exhaust)
Default States AvailableNormally Open (NO) or Normally Closed (NC)
Functionality Upon EnergizationCan block all ports (closed-center), connect two ports while blocking third (open-center), or allow flow through all ports (tandem-center)
Application UsesSwitching between circuits, pressure maintenance/diversion in systems
Selection FactorsMedia type, flow rate requirements, pressure constraints, voltage specifications, operational environment

Bi-stable Solenoid Valves

Bi-stable solenoid valves, or “latching” solenoid valves as they are sometimes known, represent a class of valve technology designed for applications requiring minimized energy consumption. These valves maintain their position—open or closed—without the constant application of electrical power; they are actuated by a momentary pulse.

What distinguishes bi-stable solenoid valves from their single stable counterparts is the inclusion of permanent magnets in their construction. These magnets serve to hold the valve in its last commanded position after the actuating electrical pulse has ceased. A subsequent pulse, often with reverse polarity, is required to move the valve to its opposite state.

This latching feature ensures that bi-stable solenoid valves remain either open or closed during power outages or situations when it’s not feasible to continuously supply power. Thus, they find widespread use in battery-powered applications and where energy savings are a significant consideration.

In terms of control, such valves require an electric control circuit capable of providing the correctly polarized pulse when a change of state is needed. This necessity adds complexity to the overall control system but substantially reduces energy costs in long-term operation.

For industries and systems in which energy efficiency is paramount and intermittent operation is acceptable or desired, bi-stable solenoid valves offer an attractive balance between performance and power conservation.

FeatureDescription
DesignationBi-stable (Latching) Solenoid Valves
ActuationMomentary electrical pulse
Power RequirementNo continuous electrical power required
Position MaintenanceMaintained via permanent magnets
Energy ConsumptionSignificantly reduced for long-term operation
Change of StateRequires subsequent pulse with reverse polarity
UsageIdeal for battery-powered systems & applications requiring efficiency
ComplexityHigher control system complexity due to polarized pulses

How do you tell if a solenoid valve is normally open or closed?

Determining whether a solenoid valve is normally open (NO) or normally closed (NC) can be achieved through several methods.

Firstly, the physical inspection of the valve when unpowered could provide an initial indication; NO valves will allow fluid to pass through without energization, whereas NC valves will block fluid flow until they are activated.

Another method involves consulting the valve’s datasheet or manufacturer specifications which should clearly state the default state of the valve. Additionally, observing the position of the actuator or stem when no electrical power is supplied to the coil can also signify its normal state; for NC valves, these components typically project outwards due to spring action as they close off flow and retract when powered. Conversely, NO valves have actuators that stay retracted until energized. If none of these methods yield conclusive results, using a multimeter to test for continuity through the valve ports when de-energized may confirm its state—continuity suggests a NO configuration while no continuity indicates an NC one.

To succinctly summarize:

IndicatorNormally Open ValveNormally Closed Valve
Physical Flow InspectionAllows fluid pass-throughBlocks fluid pass-through
Manufacturer SpecificationsStated as “Normally Open”Stated as “Normally Closed”
Actuator/Stem PositionRetracted when unpoweredProjected outwards
Multimeter Continuity TestContinuousDiscontinuous

Can you change a normally closed solenoid valve to normally open?

Converting a normally closed solenoid valve to a normally open configuration is generally not recommended or possible without redesigning the valve system. Fundamentally, the operational design and components are specific to each type of solenoid valve. Normally closed valves are designed to remain shut until an electrical signal prompts them to open, while normally open valves operate under the opposite principle. The construction differences involve the arrangement of springs, seals, and electromechanical actuators that define their default states.

Attempted modification could result in malfunctions, reduced reliability, and safety concerns; especially considering the precise tolerances and specifications each component within the valve must adhere to for proper operation. When choosing a solenoid valve for an application where both types could be applicable, it’s essential to consider factors like failure states or energy conservation prior to installation rather than attempting post-installation modifications.

The necessity for proper selection underscores why comprehensive knowledge about the application’s demands and understanding whether a normally open or normally closed solenoid valve will be most suitable are critical during the design phase itself. If a change in operation mode is necessary after installation due to system requirements adjustments, it is usually more practical—and certainly safer—to replace the existing valve with one that has the desired default state.

In conclusion

In summarizing the distinctions between normally open (NO) and normally closed (NC) solenoid valves, it is essential to recognize that the choice of valve type hinges on the specific operational requirements and safety considerations of your application.

For help in selecting the ideal solenoid valve for your needs or to explore our extensive range of fluid control solutions, we invite you to reach out to our expert team. Feel confident in making an informed decision with our guidance, ensuring that your systems operate both efficiently and reliably.